Pages

Aug 11, 2011

TNB's Term For Newbies

For those who are newbies with working related with Tenaga Nasional Berhad, this are few technical term that commonly used.


No.
Term
Definition
1
Transmission Facility
The transmision substation and/or line cable equipment (66kV and above) or part thereof. It shall also include the distribution equipment in the transmission substation.
2
Site Acceptance Test (SAT)
Pre-commissioning test performed on the transmission facility before PIAT
3
Pre-commissioning Inspection and Testing (PIAT)
Quality Assessment activity performed by PCU after the successful completion of SAT to determine the readiness of the Transmission Facility to be energised.
4
Primary Injection
Testing by means of injecting current into the primary circuit to verify the CT Ratio, CT Polarity and the CT secondary circuits. It is not being considered as a stability test.
5
Stability Test
It is the test to asess unit protection as a complete scheme thatremain unstable for all out-zone faults and operate only for in-zone faults.
6
Unit Protection
Protection system with a clearly defined zone of protection and it is usually demarcated betwenn 2 or more sets of CT's.
7
On-Load Test
It is the test  or measurement for by means of using the energised secondary voltage and secondary load current after a circuit has been energised.
8
Live Plant
A fenced area with energised high voltage equipments.
9
Live Bay
A transformer, line/cable, bus coupler or bus section bay that being energised at high voltage. Since the word is "LIVE", those equipments basically is not isolated or earthed.
10
Electrical Service Engineer
A person who being certified by Energy Commission to carry-out the work.
11
PTT
Protection, Telecommunication & Telecontrol Department in TNB Transmission Division.