KA is the amperage value (in Kilo Amp) for the fault current.
Fault current, also called "short-circuit current" (ISC) (and sometimes called symmetrical fault current) describes current flow during a short.
It passes through all components in the affected circuit. Fault current is generally very large and, therefore, hazardous which due to "fault condition" caused by the low-impedance, phase-to-phase or phase-to-ground connection.
The electrical distribution system should be designed to minimize the effect of a fault. When we experience a fault on an electrical system, the protection equipment will detect the fault and trip out the faulty circuit. It cannot however trip instantaneously, and a delay, (of up to a few seconds) will occur.
In a simple word, it prevents a short at an outlet from shutting down power to the entire building!
The formula for the short circuit current (ISC) withstand capability of an electric cable is:
Where:
Isc = Short circuit rating of cable (kA)
A = Area of conductor (mm²)
t = Time to trip (in seconds)
K = 96 for PVC, Copper conductor
= 62 for PVC, Aluminium conductor
= 116 for PAPER, Copper conductor
= 78 for PAPER, Aluminium conductor
= 143 for XLPE, Copper conductor
= 98 XLPE, Aluminium conductor
Isc = Short circuit rating of cable (kA)
A = Area of conductor (mm²)
t = Time to trip (in seconds)
K = 96 for PVC, Copper conductor
= 62 for PVC, Aluminium conductor
= 116 for PAPER, Copper conductor
= 78 for PAPER, Aluminium conductor
= 143 for XLPE, Copper conductor
= 98 XLPE, Aluminium conductor
Example: For a 70mm², PVC insulated Copper conductor, the 1 second short circuit rating is:
If the protection is fast, (say 0.2 seconds) then the conductor will have a 0.2 second short circuit rating of: